The management of single line-to-ground (SLG) failures in 11kV distribution
networks is important for the dependability of electrical system and the safety of
equipment. In this study, an adaptive control technique for a thyristor driven
Petersen coil to reduce capacitive fault currents by maintaining a resonance state
is proposed. A detailed model of an 11kV network was constructed using
MATLAB/Simulink and a PID based controller was used to vary the thyristor
firing angle (α) dynamically. The simulation findings show that the suggested
system can effectively deal with the fault transients, where a large fault current
spike (around 2300A) has been successfully suppressed. In order to get the best
compensation, the firing angle was changed by the adaptive algorithm from an
initial value of (80°) to a steady state value of (130°). Moreover, the error between
the expected setpoint and the actual RMS value converged to zero in less than 8
seconds, confirming the stability and the robustness of the control rule. This work
demonstrates the benefits of adaptive compensation over fixed-parameter coils to
enhance the transient stability and fault resilience of current distribution grids.
Keywords: Petersen Coil, Adaptive Control, Thyristor Firing Angle, 11kV
Distribution Network, Ground Fault Mitigation, MATLAB Simulink